Mainly introduces the transformation example for Tangshan, Hebei province Qian 'an Xinda iron & steel Co. LTD. Through the technical analysis and test verification of the transformation, it is shown that the energy saving effect is obvious after using the MV frequency drives system, and the operating condition of the equipment is also greatly improved.

During the process of smelting, hot molten iron and the air produce a great deal of flue gas. The smoke will pollute the environment, and it will cause harm to the workers on site. In order to reduce pollution and improve the working environment, it is necessary to add dust removal fan to the smelting furnaces.


 ME800 MV Drive in Steel .pdf


1. Dust removal fan process

In the process of smelting in a steel plant, each smelting cycle can be divided into different time periods, in different time periods; the work of the dust removal fan will also be different. We use Hebei Tangshan Qian an Xinda iron & steel Co.LTD as example.

The converter primary dust removal system has two sets of dust removal fans, one of which is used as standby;

The secondary dust removal system has a dust removal fan.

 

The converter blowing process is as follows:

A to B is the time for adding iron and scrap, about 2 minutes;

B to C is the fan speed time, about 30 seconds, adjustable;

C to D is oxygen blowing time, about 15 minutes;

D point fan starts to decelerate, about 30 seconds, adjustable;

D to E is the sampling time for temperature measurement in the furnace, about 2 minutes;

E to F is tapping times, about 2 minutes;

F to G is slag splashing time, about 3 minutes;

The entire blowing process cycle is about 25 minutes, of which the high-speed time (C to D) is 15 minutes.


ME800 MV Drives Steel Industry Solutions

Figure 1 Blowing process cycle


There are high requirements for dust removal during the oxygen blowing process, and the dust removal fan is required to run at high speed. However, in the process of adding iron and scrap steel, temperature measurement and sampling in the furnace, tapping, and slag splashing, the requirements for dust removal are lower, low speed is enough. According to the actual measurement, the rise and deceleration time of the dust removal fan can be combined with the calculation of the low speed operation time, which has less influence on the result.


2. Transformation solution 

2.1 System parameters

Motor model

YKK500-2

Rated voltage

10KV

Ranted current

51.9A

Rated power

800KW

Rated power factor

0.87

Rated speed

2985rpm

Actual working current

30~32A

Actual power factor

0.82

Manufacturer

Jiangsu Xianda explosion-proof motor co. LTD

Table 1 parameters of the primary dust removal fan nameplate


Motor model

YKK500-6

Rated voltage

10KV

Ranted current

45.2A

Rated power

630KW

Rated power factor

0.856

Rated speed

994rpm

Actual working current

40~45A

Actual power factor

0.83

Table 2 parameters of the secondary dust removal fan nameplate


Besides:

Annual running hours of primary dust removal fan: 7500h;

Annual running hours of secondary dust removal fan: 5000h;

Electricity price: 0.5 yuan / kWh

Before the transformation, the dust removal system mainly used a hydraulic coupler to adjust the operation speed of the dust removal fan. There were disadvantages such as poor control accuracy, narrow speed adjustment range, low efficiency, and large loss.


2.2 Speed control requirements

This project adopts two sets of medium-voltage frequency drives equipment produced by Shanghai STEP Electric Co., Ltd., ME800-0800-T10-PA for primary dust removal fan and ME800-0630-T10-PA for the secondary dust removal fan.

The dust removal fan has two main working states. Correspondingly, the drives presets two speed points. Speed point 1 corresponds to the high speed operation status of the dust removal fan, and speed point 2 corresponds to the low speed operation status of the dust removal fan. After field measurement, for the first dust removal fan: when the input frequency is 40Hz, the dust removal fan can be guaranteed to run at a high speed; when the input frequency is 25Hz, the dust removal fan can be kept at a low speed. For the secondary dust removal fan: when the input frequency is 45Hz, the dust removal fan can be guaranteed to run at a high speed; when the input frequency is 25Hz, the dust removal fan can be guaranteed to run at a low speed. In each blowing process cycle, the proportion of dust removal fan working at high speed is: 15/25 = 60%; the proportion of dust removal fan working at low speed is: 1-60% = 40%. At the same time, due to the different roles of the primary fan and the secondary fan, their actual operating conditions also differ. The details are as follows:

Speed point

Fan model

Fan operating state

Corresponding frequency

Proportion

1

Primary fan

High speed

40Hz

60%

2

Primary fan

Low speed

25Hz

40%

1

Secondary fan

High speed

45Hz

60%

2

Secondary fan

Low speed

25Hz

40%

Table 3 operating state diagram of the dust fan


At the same time, the drives also provides excellent HMI.

The staff can modify relevant parameters through the HMI according to the field conditions, and adjust the running state of the dust removal fan in time to ensure the dust removal effect.


2.3 System configuration and site photos

According to the site working conditions and motor technical parameters, our company is equipped with two ME800 series medium -voltage drivess on the site after field inspection, the models are: ME800-0800-T10-PA * 1, ME800-0630-T10-PA * 1 and equipped with an automatic bypass system to ensure the safety and continuity of production.

FIG. 2 Automatic bypass cabinet


The automatic bypass system is mainly composed of three vacuum contactors: KM1, KM2, and KM3. KM2 and KM3 have a mechanical interlock function and cannot be closed at the same time to protect the drives.

● In the frequency conversion state: KM1 and KM2 are closed, KM3 is open, and the load runs in the frequency conversion state;

● In the power frequency state: KM1 is disconnected from KM2, KM3 is closed, and it runs in the load power frequency state.

3. Energy-saving effect

3.1 Power consumption of dust removal fan before transformation

According to the operation parameters in table 1 ~ 4, it can be obtained:

(1) The annual power consumption of the first dust removal fan

ME800 MV Drives Steel Industry Solutions


(2) The annual power consumption of the secondary dust removal fan

 ME800 MV Drives Steel Industry Solutions


3.2 Power consumption of dust removal fan after transformation

After transformation, the power consumption calculation is performed according to the engineering experience formula.

(1) Annual power consumption of the first dust removal fan

When the dust removal fan runs at a frequency of 40Hz, the speed is 2450rpm.


(2) Annual power consumption of the secondary dust removal fan

According to on-site calculations, when the dust removal fan runs at a frequency of 45Hz, the speed is 900rpm.


3.3 Energy-saving effect


3.4 On-site energy saving operation data

STEP performed a comparative test on the power consumption of the motor under the power frequency condition and the frequency conversion condition. The details are as follows:

Medium-voltage drives model

ME800-0800-T10-PA

ME800-0630-T10-PA

Load type

First dust removal fan

Secondary dust removal fan

Motor power

800KW

630KW

Running condition

In power frequency state

In frequency conversion state

In power frequency state

In frequency conversion state

Starting time

2011/4/20

12:15

2011/4/21

10:27

2011/4/24

12:15

2011/4/23

10:27

Meter reading

1431.3

1418.1

473.1

454.8

Finish time

2011/4/20

18:15

2011/4/21

16:27

2011/4/24

18:15

2011/4/23

16:27

Meter reading

1432.2

1418.8

475

456.1

Total power consumption(KWh)

0.9×4000=3600

0.7×4000=2800

1.9×2000=3800

1.3×2000=2600

Average power consumption (per hour)

3600/6=600

2800/6=437

3800/6=634

2600/6=434

Energy saving per hour(KWh)

600-437=163

634-434=200

Power saving rate

163/600=27.2%

200/634=31.5%


The electricity price is calculated at 0.5 yuan / KWh, and the annual electricity savings are:

(1) Electricity saving of the first dust removal fan: 163 × 7500 × 0.5 = 61.125 million yuan(86,692 USD)

(2) Electricity saving of the secondary dust removal fan: 200 × 5000 × 0.5 = 50 million yuan(70,913 USD)

Total: The annual electricity saving is 111,125 million yuan(157,605 USD).